Pathlight VX Site Preparation Guide 17
Customer Ecosystem Checklist
Table 6 lists questions that help verify that the customer’s ecosystem is ready for the installation.
Verifying Site Requirements
This section lists requirements for the Pathlight VX installation site, including environmental, power, rack,
tool, and local area network (LAN) connection pre-requisites.
Verifying Environmental Requirements
This section lists the operating and non-operating temperature ranges for the Pathlight VX.
Table 7
lists temperature and humidity requirements for the installation site.
Table 6 Customer Ecosystem Checklist
Readiness Question
Has the customer disabled Test Unit Ready (TUR) Requests on Windows 2000 and
Windows Server 2003 Systems [required]? Refer to “Configuring the Pathlight VX” in the
Pathlight VX Installation Guide. Also consult this bulletin: https://csweb01hq.adic.com/
bulletins/pvx_bul/60025.pdf
Are Single Initiator Zoning practices implemented [best practice]?
Is HBA Persistent Binding enabled [best practice]?
Have you verified that disks are dedicated to a single HBA, and tapes are likewise
dedicated to a single HBA (there is no concurrent disk and tape on a single HBA) [best
practice]? Refer to https://csweb01hq.adic.com/bulletins/misc_bul/Info3.htm
Can the customer allow iLink outbound connectivity?
Refer to: http://www2.adic.com/ilink/
Specify the customer-preferred Remote Connectivity Option: Webex or Modem.
Pathlight VX customers have the option of allowing either Webex or a modem for ADIC
to remotely connect to the Pathlight VX head and EMC to remotely connect to the
Navisphere host. The preferred method for connectivity is Webex. If the customer
chooses the modem option, EMC will need to be directed to configure the modem at time
of the PVX/EMC disk subsystem installation. If neither of these options is acceptable
to the customer, a Service Uplift fee will be required.
Table 7 Temperature and Humidity Requirements for the Installation Site
Operating State Temperature Humidity Altitude
Operating 15 to 32
°C
(59 to 90°F)
20 to 80% non-condensing –60.96 to 3,048 m
(-200 to 10,000 ft.)
Non-operating –40 to 70
°C
(–40 to 158°F)
10 to 90% non-condensing –60.96 to 12,192 m
(–200 to 40,000 ft.)