12-88 6-00667-01 Rev B
Scalar 100
04 xx
Type 4 Software errors (Inter Processor) including Microcode and
Operating System errors.
Power Off and On the Scalar 100 Library to recover from the error. Use the Rear
Switch to perform this action, wait at least one minute between power Off and
On.
05 xx
A permanent Operating System error occurred.
Power Off and On the Scalar 100 Library to recover from the error. Use the Rear
Switch to perform this action, wait at least one minute between power Off and
On.
Contact ATAC.
10 xx
Barcode scanner communications failed.
Retry the failing operation.
Power Off and On the Scalar 100 Library to recover from the error. Use the Rear
Switch to perform this action, wait at least one minute between power Off and
On.
Contact ATAC
11 xx
Barcode scanner communication is OK, data received from the Barcode
scanner is bad.
Ensure that the barcode label was supplied by ADIC or an ADIC approved
vendor.
Contact ATAC.
13 xx
Cannot read Barcode label or the label is bad.
Ensure that the barcode label was supplied by ADIC to an ADIC approved
vendor.
Check the cartridge labels to ensure that they meet specifications, are properly
installed, and not damaged or dirty. The cartridge slots in question are displayed
with the Service Action Code.
Ensure that scan beam is not obstructed.
Retry the failing operation.
Power Off and On the Scalar 100 Library to recover from the error. Use the Rear
Switch to perform this action, wait at least one minute between power Off and
On.
Contact ATAC.
Reported
SAC
Error and Solution