
Chapter 5 Service Commands
Testing the Library
80 ATL P1000 Series User’s Guide
Procedure (continued)
3
Select all desired test options:
•
To swap cartridges randomly, press the Random button.
If you do not press this button, cartridges are swapped
sequentially from the first bin or drive.
•
To have the library read the bar code as it swaps each cartridge,
press the Use Barcodes button.
•
To have the test run continuously until aborted, press the
Continuous button. Otherwise, enter the number of times you
want the test to run into the # of Runs box.
4
When you have selected the test and all test options, press the
Execute button.
The GUI displays a “Command In Progress” screen.
To cancel the system test, press the Abort button.
Note:
If you selected the Continuous option in step 3, you must press
the Abort button to stop the test.
Performing a Service
Calibration
5
The Service Calibrate command autocalibrates the library (the tape
drives, the cartridge bins, and the load port) and saves the target
locations as a baseline for all subsequent calibration procedures.
Note:
Before performing a service calibration, remove all tape cartridges
from the library.
To perform a service calibration, press the Calibrate Library button on
the Service screen. The GUI displays a “Command In Progress” screen
during the calibration process.
To cancel the calibration process, press the Abort button.
Commentaires sur ces manuels