Chapter 6 Maintaining Your Library
Maintenance Actions
Scalar i6000 User’s Guide 442
Vertical Alignments 6
The vertical alignments graphical report shows the results for test of
vertical alignment of tape magazines on the drive-side and door-side of
each frame, and for vertical alignment of each I/E station.
If the graphical report shows a failed result for the drive-side or door-
side, make sure that all tape magazines are installed properly on that
side and that the calibration targets are correctly snapped on to the
magazines.
If the graphical report shows a failed result for the I/E station, make
sure the I/E station and front door are completely shut.
If running the test again still generates failed results, realign the
middle X-axis rail and check the alignment of the top and bottom X-
axis rails at the location of the failure.
See figure 41 on page 443.