Scalar 24 Installation and Operation Guide 135
Vital Product Data Recovery
The Vital Product Data feature allows library settings to be automatically stored on the RMU. The feature
prevents customized settings, such as slot configurations, from being lost when the main board is replaced.
This feature works with LTO drive types only.
Environmental Considerations
For best performance of your Scalar 24, and to minimize the chance of condensation, please observe the
following guidelines:
Install your Scalar 24 on a level surface. Do not place the Scalar 24 on a carpeted surface.
If you expose cartridges to temperatures outside the operating limits, (see Specifications), stabilize
them by leaving the cartridges in the operating temperature for a minimum of two hours before you
use them.
E2h Security Alert
Check Door
The system has detected
operator interference, such as
an open door and magazine
removal, or a host has issued
a PREVENT MEDIA
REMOVAL and a tape has
been inserted or removed
from the I/E slot.
Check and ensure that
magazines are installed, the
door is closed, and that the
I/E slot is empty.
E3h,
E4h,
E5h, and
E6h
SCSI Error
Check SCSI
A SCSI connection problem
has been detected.
Make sure the cables are
connected correctly, the bus
type, LVD is connected
correctly, and the proper
terminator is applied.
F5h Clean Needed
Check Drive X
A drive has been cleaned, but
still requires cleaning. The
cleaning tape may not
function properly, may be
expired, or the drive may be
defective.
Retry the clean operation.
F6h Tape Expired
Eject Slot X
A cleaning tape is expired. Export the cleaning tape and
insert a new one.
F7h No Clean Tape
Insert Tape
A cleaning operation was
attempted, but a cleaning
tape is not configured,
expired, or not available.
Insert a cleaning tape into the
I/E slot or configure a
cleaning slot and import a
cleaning tape into that slot.
F8h Tape Missing
in Slot X
A previously configured
cleaning tape is no longer
found. It may have been
removed manually, loaded in
a drive, or placed in a data
slot.
Place the tape back into the
slot.
SAC
Code
Error Message Description Recommended Action